Ten Permeability
Nanosox HVAC duct adopts Unique micro-permeability technology - Small Permeability as 3.6 m3/m2/h (0.2 cfm/ft2) is available to strike a proper balance between anti-condensation and energy-saving, only a small percentage of airflow is permeated from fabric surface for anti-condensation, most air is discharged from precisely calculated orifice towards the targeted area in a very fast pace, which reduces energy wasting at high space.
Property | Items | Application | Requirement | Index | Code Compliance | Remarks | |
Material property | Permeation | Error rate of permeation index <5% (under 125pa or at 0.5w.g) | Ventilation area: e.g. gym ventilation | Non-permeable Omm/s | GB/T5453-1997 | National textile products quality supervision and inspection center | To make sure the air dispersion performance, the permeability should be selected carefully according to the installation height, air volume, air pressure and condensation free and energy saving |
High and large space/space with fast end air velocity | Micro-permeability 1,2,5mm/s | ||||||
Middle or low space/space with slow end air velocity | Medium-permeability 10,20,30mm/s | ||||||
Low space/slow end air velocity | Large-permeability 40,80,100mm/s | ||||||
Fire safety | B | Above the ground | Wash durability 50 times B-s1,d0, t0 Smoke Toxicity ZA Class1 | GB 8624-2012 GB20286-2006 EN13501-1:2007 | National fireproof construction material quality supervision and inspection center | Product quality tracking; Certification of fire retardant identity in public places Wash durability 50 times | |
A2 | High-rise/basement/strict fire safety space | A2-s1,d0,t0 | GB 8624-2012 | National fireproof construction material quality supervision and inspection center | Formal testing | ||
Other physical properties | Clean and fiber shedding | All application area | No particle detachment | Ac167 and UI181 | UL | Formal testing | |
Mildew resistance | All application area | During the 60 days UL 181 test, no microbial breakage or decomposition | |||||
Health and safety of textiles | All application area | PH4.0-7.5 Formaldehyde content<=20mg/kg no peculiar smell. | GB18401-2003 | National textile products quality supervision and inspection center | |||
Product Property | Pressure resistance | Under the static pressure of 1900pa,no change of the sample | No change | Ac167 and UL 187 | UL | Formal test and approval |
Property Items | Index | Results | Code Compliance | ||
Material Property | Fire safety | B/S1/d0/t0 Class 1&Class0 | B1(B-s2,d0,t0) | GB8624-2012 EN13501-1:2007 UL 2518 BS 476-6,7:1997 | |
Thermal conductivity | 0C(average temperature),<=0.036 | 0.033 | GB/T 17794-2008 ASTMC 177/C518-10 | ||
Moisture Permeability | water vapor permeability | <=1.3 X 10 -10g/(s.m.Pa) | 1.0 x 10^-10 | ASTME96-10 | |
Moisture resistance factor | >=1.5x10^3 | 2 x 10^4 | ASTEM96-10 | ||
Water absorption(by volume) | <=0.3% | 0.17% | ASTMC209-07 | ||
Product performance | Pressure resistance | When the pressure reaches 2000pa, the product is normal without any breakage | No change | AC 167 & UL 181 | |
Air leakage volume (m^3/h.m^2) | When inner static pressure is 5000pa, the leakage per unit area Qa<=3 | 0.31 1.34 | JGJ141-2004 | ||
When inner static pressure is 1000pa, the leakage per unit area Qa<=1.57 | |||||
Durability | Air leakage after durability test is less than 80% of the air leakage before the best | 37% | JG/T258-2009 | ||
Anti-condensation | There is no condensation at the duct surface, flange joint, and support reinforcement | Condensation free | JG/T258-2009 |